The Assessment and Characteristics for Indoor Air Quality in Military Barracks |
Suk-Bong Kim, Sang-Jo Jeong, Sang-Ho Baek, Tae-Wook Kim, Young-Jun Park |
군 병영시설의 실내 공기질 평가 및 특성 |
김석봉, 정상조, 백상호, 김태욱, 박영준 |
육군사관학교 토목환경학과 |
|
Abstract |
In this study, the Indoor Air Quality(IAQ) in military barracks is evaluated and its characteristics is discussed as well. The military barracks of R.O.K Army are categorized into three types and the IAQ in these individual facilities is measured for 24 hours both in summer and winter. Test results show that the particulate matters($PM_{10}$) and carbon dioxide($CO_2$) were the main causes contaminating IAQ in military barracks. While $CO_2$ can be purified by ventilation, adequate facilities have to be installed in case of the new type of combination barracks to remove $PM_{10}$. In addition, to improve the living condition of military barracks and to recover IAQ in new combination style barracks which is planned to complete by 2011, a standard or law regulating IAQ in military barracks has to be established. |
Key Words:
IAQ(Indoor Air Quality), Military Barracks$CO_2$$PM_{10}$ |
|